FUNCTIONAL TESTING AFTER REPAIR
Following
repair, and before inspection plates, cover plates, or upholstering are replaced,
test the entire system.
Open the cylinder valve slowly and observe the
pressure gauge on a high-pressure system. A pressure of approximately 1,800 psi
(at 70 °F) should be indicated on the gauge. (Cylinder pressure will vary
considerably with radical temperature changes.)
(1) Check the system by installing one of the mask hose fittings
(minus the mask) in each of the cabin wall outlets to determine whether there
is a flow. If a demand mask is used, check by breathing through the mask and,
if appropriate, clean the mask according to paragraph 7.9.4.
(2) Check the complete system for leaks in accordance with the
procedure outlined in paragraph 9-49b(2)(d).
(3) If leaks are found, close the cylinder valve and open an
outlet to reduce the pressure in the system to zero.
The following checks may be made for a pressure drop check of the system.
(1) Open the cylinder valve and pressurize
the system. Observe the pressure gauge (a pressure of approximately 1,800 psi
at 70 °F should be indicated). For the light weight ICC 3HT 1850 cylinders,
pressurize the system to approximately 1,850 psi at 70 °F.
(2) Close the cylinder valve and wait
approximately 5 minutes for temperatures to stabilize.
(3) Record the pressure gauge reading
and temperature and after 1 hour, record the pressure gauge reading and
temperature again.
(4) A maximum pressure drop of 100 psi
is permissible.
NOTE: Conduct the above tests in an area where changes of temperature will be
less than 10 °F. If a leak occurs during the 1-hour period, suitable
corrections would be required, or reconduct the test under conditions of
unvarying temperatures.
SERVICE REQUIREMENTS OXYGEN
CYLINDERS:
Standard-weight cylinders must be hydrostatic tested at the end of each 5-year
period. This is a Department of Transportation (DOT) requirement. These
cylinders carry an ICC or DOT 3AA 1800 classification and are suitable for the
use intended: The lightweight cylinders must be hydrostatic tested every 3
years, and must be retired from service after 24 years or
4,380 pressurizations, whichever occurs first. These cylinders carry an ICC or
DOT 3 HT 1850 classification and must be stamped with the approval after being
inspected.
CAUTION: Use only aviation breathing
oxygen when having the oxygen bottle charged.
Charging High-Pressure Oxygen
Cylinders:
The following are recommended procedures for charging high-pressure oxygen
cylinders from a manifold system, either permanently-installed or
trailer-mounted.
CAUTION: Never attempt to charge a low-pressure cylinder directly from a
high-pressure manifold system or cylinder.
(1) Inspection. Do not attempt to charge oxygen
cylinders if any of the following discrepancies exist:
(a) Inspect for contaminated fittings on
the manifold, cylinder, or outside filler valve. If cleaning is needed, wipe
with stabilized trichloroethylene and let air dry. Do not permit the solvent to
enter any internal parts.
(b) Check the hydrostatic test date of
the cylinder. DOT regulations require ICC or DOT 3AA designation cylinders to
be hydrostatic tested to 5/3 their working pressure, every 5 years. Cylinders
bearing designation ICC or DOT 3HT must be hydrostatic tested to 5/3 their
working pressure every 3 years, and retired
from service15 years or 4,380 filling cycles after the date of manufacture,
whichever occurs first.
(c) If the cylinder is completely empty, do not charge. An empty cylinder
must be removed, inspected, and cleaned before charging.
(2) Charging:
(a) Connect the cylinder valve outlet or the outside filler valve to the
manifold.
(b) Slowly open the valve of the cylinder to be charged, and observe the pressure
on the gauge of the manifold system.
(c) Slowly open the valve of the cylinder on the manifold system having the
lowest pressure and allow the pressure to equalize.
(d) Close the cylinder valve on the manifold system and slowly open the valve
of the cylinder having the next highest pressure. Continue this procedure until
the cylinder has been charged in accordance with
.
(e) Close all valves on the manifold system.
(f) Close the valve on the filled cylinder and remove the cylinder from the
manifold.
(g) Using a leak detector, test for leakage around the cylinder valve
threaded connections. (If leakage is present, discharge the oxygen and return
the cylinder to the facility for repair.)
(h) Let the cylinder stabilize for a period of at least 1 hour, and then
recheck the pressure.
(i) Make any necessary adjustments in the pressure.
Charging
of Low-Pressure Oxygen Systems and Portables. For recharging a low-pressure
aircraft oxygen system, or portable cylinders, it is essential that the oxygen
trailer or cart have a pressure-reducing regulator. Military types E-2 or C-1
reducing regulators are ` satisfactory. These types of regulators reduce the
large cylinder pressure from 2,000 psi to a line pressure of 450 psi. (A welding pressure-reducing regulator is not
satisfactory.)
CAUTION: When refilling the low pressure system or
portable cylinders, open the oxygen filler tank valve slowly to allow the
system or portable cylinders to be filled at a slow rate. After the refilling
operation is completed, check for leaks with a leak detector.