FIRE
DETECTION AND EXTINGUISHER SYSTEM
- MAINTENANCE PRAC TICES\
INTRODUCTION
Fire
detector sensing elements are located in many high-activity areas around
aircraft engines. Their location, together with their small size, increases
the chances of damage to the sensing elements during maintenance. The
installation of the sensing elements inside the aircraft cowl panels provides
some measure of protection not afforded elements attached directly to the
engine. On the other hand, the removal and re-installation of cowl panels can
easily cause abrasion or structural defects to the elements. A well-rounded
inspection and maintenance program for all types of continuous-loop systems
should include the following visual checks. These procedures are provided as
examples and should not be used to replace approved local maintenance
directives or the applicable manufacturer's instructions.
FIRE DETECTION MAINTENANCE PRACTICES
Sensing
elements should be inspected for:
(1) Cracked or broken sections caused by
crushing or squeezing between inspection plates, cowl panels, or engine
components.
(2) Abrasion caused by rubbing of
element on cowling, accessories, or structural members.
(3) Pieces of safety wire or other metal
particles which may short the spot detector terminals.
(4) Condition of rubber grommets in
mounting clamps, which may be softened from exposure to oils, or hardened from
excessive heat.
(5) Dents and kinks in sensing element
sections. Limits on the element diameter, acceptable dents or kinks, and
degree of smoothness of tubing contour are specified by manufacturers. No
attempt should be made to straighten any acceptable dent or kink, since stresses
may be set up that could cause tubing failure. (See illustration of kinked
tubing in figure 5.1).
(6) Loose nuts or broken safety wire at
the end of the sensing elements (figure 5.2). Loose nuts should be
re-torqued to the value specified in the manufacturer's instructions. Some
types of sensing element connections require the use of copper crush gaskets.
These gaskets should be replaced any time a connection is separated.
(7) Broken or frayed flexible leads, if
used. The flexible lead is made up of many fine metal strands woven into a
protective covering surrounding the inner insulated wire. Continuous bending of
the cable or rough treatment can break these fine wires, especially those near
the connectors. Broken strands can also protrude into the insulated gasket and
short the center electrode.
(8) Proper sensing element routing and
clamping (figure 5.3). Long unsupported
sections may permit excessive vibration which can cause breakage. The distance
between clamps on straight runs is usually about 8 to 10 in., and is specified
by each manufacturer. At end connectors, the first support clamp is usually located
about 4 to 6 in. from the end connector fittings. In most cases, a straight run
of 1 in. is maintained from all connectors before a
bend is started, and an optimum bend radius of 3 in. is
normally adhered to.
(9) Rubbing between a cowl brace and a sensing element (figure 5.3). This interference, in
combination with loose rivets holding the clamps to skin, may cause wear and
short the sensing element.
(10) Correct grommet installation.
The grommets are installed on the sensing element to prevent the element from
chafing on the clamp. The slit end of the grommet should face the outside of
the nearest bend. Clamps and grommets (figure
5.4)
should fit the element snugly.
(11) Thermocouple detector mounting brackets
should be repaired or replaced when cracked, corroded, or damaged. When
replacing a thermocouple detector, note which wire is connected to the
identified plus terminal of the defective unit and connect the replacement in
the same way.
(12) Test the fire detection system for
proper operation by turning on the power supply and placing the fire detection
test switch in the "TEST"
position. The red warning light should flash on within the time period
established for the system. On some aircraft an audible alarm will also sound.
In addition, the fire detection circuits are checked for
specified resistance and for an open or grounded condition. Tests required
after repair of replacement of units in a fire detection system or when the
system is inoperative include:
(i) Checking the polarity,
ground, resistance and continuity of systems that use thermocouple detector
units, and
(ii) Resistance and
continuity tests performed on systems with sensing elements or cable detector
units.
In
all situations follow the recommended practices and procedures of the
manufacturer of the type system with which you are working.
No comments:
Post a Comment